City of Lakeland Local Limits Table


Chapter 102 of the City of Lakeland Code

April 20218

  Glendale WRF   Northside WRF   West Lakeland WLRF (1)  
Parameter Chronic* TRC**   Chronic* TRC**   Chronic* TRC** Units
Arsenic 0.235 0.282   0.047 0.0564   0.235 0.282 mg/L
Cadmium 0.02 0.024   0.012 0.0144   0.02 0.024 mg/L
Chromium 1.21 1.452   2.26 2.712   1.21 1.452 mg/L
Copper 0.103 0.1236   0.167 0.2004   0.103 0.1236 mg/L
Cyanide 0.069 0.0828   0.084 0.1008   0.069 0.0828 mg/L
Lead 0.301 0.3612   0.207 0.2484   0.301 0.3612 mg/L
Mercury 0.00475 0.0057   0.0024 0.00288   0.00475 0.0057 mg/L
Molybdenum 0.25 0.30   0.099 0.1188   0.25 0.30 mg/L
Nickel 0.820 0.984   0.44 0.528   0.820 0.984 mg/L
Selenium 0.033 0.0396   0.052 0.0624   0.033 0.0396 mg/L
Zinc 0.816 0.9792   1.41 1.692   0.816 0.9792 mg/L
Silver 1.56 1.872   0.0175 0.021   1.56 1.872 mg/L
BOD 2380 3332   2300 3220   (2) (2) mg/L
pH 5.5 - 10.5 5.5 - 10.5   5.5 - 10.5 5.5 - 10.5   5.5 - 10.5 5.5 - 10.5 mg/L
Conductivity 3135 3762   6140 7368   3135 3762 mg/L
Oil & Grease 460 644   505 707   460 644 mg/L

*Chronic values are the numerical Local Limits for the City of Lakeland.  A violation of any magnitude is a Chronic Violation.

*** TRC (Technical Review Criteria) is either 1.4 times the Local Limit for conventionals or 1.2 times the Local Limit for all other parameters.  A violation above this value is both a Chronic and a TRC violation.

(1) Local Limits for the West Lakeland WLRF are the same as the  Glendale WRF as the effluent from the WLRF goes to Glendale.

(2) The BOD limit for the WLRF shall be an allocation of the available design capacity after removing a portion for reserve for all users of the WLRF.  Each user shall be allocated a portion of this capacity in a Wastewater Discharge Permit